Fire Pro tests backflow preventers to confirm they work and are protecting your water supply. We test to Ohio plumbing code, so your water system stays safe.
- Full Operational Testing We check operation and pressure and confirm the device is doing its job of keeping contamination out of the water.
- Leak Detection We find leaks and fix them so the system stays sound.
- Certification & Compliance We give you certified test results that meet Ohio plumbing codes and local regulations.
Fire Protection Solutions does certified backflow preventer testing. The device sits between your fire protection system and the drinking water supply, and the test proves it’s keeping them apart. We test every assembly to Ohio plumbing codes and industry standards and give you certified results.
REGULAR, CODE-COMPLIANT TESTING FOR INDUSTRIAL & COMMERCIAL PROPERTIES
Backflow Preventer Testing Services in Mentor, Ohio
Our backflow testing team in Mentor has decades of experience. We test to Ohio plumbing code and your local water authority’s standards and protect the drinking water your building depends on.
We test all the major assembly types. That includes double check assemblies, reduced pressure zone (RPZ) devices and pressure vacuum breakers. We cover every part of the annual test, from differential pressure readings and check valve verification to relief valve operation. Then we file the certified test report directly with your water authority.
Testing on schedule keeps your property compliant and your water supply protected. Fire Protection Solutions in Mentor, Ohio runs your annual testing efficiently. You’ll know where things stand at every step and get full documentation. If a device fails, we find the problem on the spot and quote the repair before we leave.
Forward Flow Testing for Fire Line Backflows
The water department’s annual test proves your backflow stops water from flowing backward. If the device sits on a fire sprinkler line, it also needs a second test every year that the water department never asks about. NFPA 25, which the Ohio Fire Code adopts, requires an annual forward flow test on every backflow preventer in fire protection piping, flowed at the system demand the sprinklers were designed for.
We flow the fire line through 2 1/2 inch hose outlets on the test header downstream of the device, read pitot pressure in each stream, and record the total GPM along with static and residual pressure at the riser. The number on the report tells you, your insurer and the fire inspector whether the assembly is restricting the sprinkler supply. We bundle the forward flow test with the water department test so the device gets both in one visit. On existing backflows that have no way to flow, we design and install forward flow test manifolds. Read more in Forward Flow Testing for Fire Sprinkler Backflows.
Why Choose Us?
The annual backflow test is a small part of your building’s safety and compliance obligations, and it still has to be right. Our Mentor-based team has decades of experience. Our results are accurate and the paperwork goes through with your water authority without questions.
- Local Expertise You Can Trust We know Mentor’s water system requirements and Ohio plumbing codes, and every test we do meets local standards.
- Certified Technicians with Proven Experience Our team is factory-trained, certified and experienced with all types of backflow prevention devices.
- High-Quality Equipment We use only UL-listed or ASSE-approved backflow preventers, because they hold up and keep working.